3
WIRING
C
AUTION: power must be switched OFF before wiring the unit.
–+
IS
®
–
LOOP
CURRENT
IS
0 %
100 %
P
ositive supply to (+) terminal/HART connection
Negative supply to (-) terminal/HART connection
min 12 V DC – max 28,4 V DC (Exi) - 32 V DC (Exd)
Shield wire to green grounding screw (resistance to
ground must be < 1 Ω).
Use certified flameproof cable
gland(s) and cable for Explosion
p
roof area.
Galvanic Barrier:
Intrinsically safe units: max 28,4 V DC @ 94 mA
Not needed for General Purpose / explosion proof
models.
ANALOG I/O
or
DIGITAL I/O
(only for units with HART)
Customer supplied
local current meter
Do not connect shield
Ex
Non Ex
Ex
Non Ex
Ex
Non Ex
IMPORTANT:
The shield wire should only be grounded at ONE side only. It is recommended to connect the shield to ground in the field (at
the transmitter side - as shown above) but connecting in the control room is also allowed.
LOOP RESIST
ANCE
1200
1000
800
600
400
200
0
0
10
20
30
40 VDC
20.5 mA
24 VDC
620
11
Ω